Arc Flash PPE in Canada: Arc Ratings (cal/cm²) and What to Wear Under CSA Z462:24
Short answer: Arc flash PPE is chosen by arc rating, not by a category number. Under CSA Z462:24, the 2024 edition of Canada's workplace electrical safety standard, every arc-rated layer must carry a rating in cal/cm² that meets or exceeds the incident energy for the task, found by an incident energy analysis or the standard's table method.
An arc flash is one of the most violent hazards on any worksite. The Canadian Centre for Occupational Health and Safety (CCOHS) says the air in an arc can reach almost 20,000 °C, hot enough that clothing and skin within about a metre can ignite, melt or vaporize. The blast that follows throws molten metal and fragments and can cause falls, hearing damage and brain injury. PPE is the last line of defence, so the first question is always whether the equipment can be de-energized and locked out instead.
This guide covers one thing: how to match arc flash clothing and PPE to the hazard using arc ratings. For the basics of what arc flash is and why it happens, see our guide to arc flash and electrical safety equipment.
Start with the hazard, not the clothing
CCOHS lists the controls that come before PPE. Work de-energized whenever possible and follow lockout/tagout procedures. Where live work is justified, use guarding, approach boundaries and barricades, more working distance, non-contact test instruments, work permits and job planning. An arc flash risk assessment then sets how much incident energy a worker could face at a given task and distance. That number drives everything that follows.
CCOHS defines the arc flash boundary as the distance at which an unprotected person could receive a second-degree burn, assumed to happen at an incident energy of 1.2 cal/cm² (5 J/cm²). Anyone inside that boundary needs arc-rated protection.
What CSA Z462:24 changed: categories became minimum arc ratings
CSA Z462 is based on the U.S. standard NFPA 70E and is now in its sixth edition, Z462:24. According to CSA Group's summary of the 2024 revisions, the edition replaced every reference to an "arc flash PPE category" with an "arc flash PPE minimum arc rating". The old category tables moved to Annex V and became the "arc flash PPE selection table method".
If your procedures, labels or older training still use category numbers, here's how they line up with the 2024 wording:
| Former arc flash PPE category | Minimum arc rating in CSA Z462:24 |
|---|---|
| 1 | 4 cal/cm² |
| 2 | 8 cal/cm² |
| 3 | 25 cal/cm² |
| 4 | 40 cal/cm² |
| 5 | 75 cal/cm² |
NFPA 70E still uses PPE categories, so sites that follow U.S. practice, or equipment labels from earlier studies, may show category numbers for some time. Check which edition your arc flash study and your written program are based on before you buy.
Two ways to set the arc rating you need
- Incident energy analysis. An engineering study calculates the incident energy at the worker's working distance for each piece of equipment. The arc rating of the PPE has to meet or exceed that calculated value.
- Arc flash PPE selection table method. For equipment that falls within the table's limits (equipment type, voltage, available fault current and clearing time), the table gives a minimum arc rating directly, without a site-specific calculation.
CCOHS notes that either method can be used, but only one at a time on the same piece of equipment, never both. Ask whoever did your arc flash study which method your equipment labels follow.
How to read the arc rating on a garment label
Arc-rated garments are tested and labelled with an arc rating in cal/cm². Before a garment goes into service, check the label for:
- The arc rating in cal/cm². It must meet or exceed the minimum rating or calculated incident energy for the task.
- Whether the rating belongs to the single garment or a tested layered system. Ratings on separate labels can't simply be added together. A layered system's rating has to come from testing those layers together, as the manufacturer states.
- The standard it was tested to and the manufacturer's care instructions, because laundering and repair affect protection.

Two points cause the most mistakes. First, flame-resistant (FR) is not the same as arc-rated (AR): an arc-rated garment is flame-resistant, but a flame-resistant garment doesn't necessarily have an arc rating. Second, anything worn under arc-rated clothing must be non-melting. Polyester or nylon base layers can melt onto the skin even when the outer layer holds.
Hoodie, shirt, jacket or coverall?
The garment style matters less than its rating and coverage. Choose the style that suits the job and the season, then confirm the rating:
- Arc-rated shirts, pants and coveralls are the everyday base for electrical crews. Coveralls remove the gap at the waist.
- Arc-rated hoodies and sweatshirts add warmth, but a hoodie's fabric hood is not an arc flash hood and doesn't replace face and head protection.
- Arc-rated insulated jackets, parkas and bibs are the outer layer for cold outdoor work. Every visible outer layer must be arc-rated, including winter wear and hi-vis, so a regular parka thrown over AR clothing defeats the system.
Head, face, hands and feet
CCOHS lists the other PPE needed where there's a risk of arc flash: a hard hat (Class G or E), a face shield, balaclava or hood, safety glasses or goggles, heavy-duty leather, arc-rated or rubber insulating gloves, hearing protection and footwear. All of it must suit the energy expected.

Where there's also a shock hazard, rubber insulating gloves rated for the voltage are worn with protectors over them. Inspect rubber gloves and their protectors before every use.
Before you open the panel: a quick check
- Can the work be done de-energized and locked out instead?
- Which method set the PPE for this equipment, the incident energy analysis or the table method, and what minimum arc rating does it require?
- Does every outer layer, including hoodies, winter wear and hi-vis, carry an arc rating at or above that number?
- Is everything underneath non-melting?
- Are the face, head, hand, hearing and foot protection right for the task?
- Are rubber insulating gloves and protectors inspected and suited to the voltage?
- Is the garment clean, undamaged and laundered according to the label?
Keyline Safety's stand
An arc rating is a number you can check, so check it. The arc flash study or table sets the minimum, and every layer a worker wears, from a winter parka to a hoodie, has to meet it. Buying "FR clothing" without that number, or covering AR gear with an ordinary jacket, leaves workers less protected than they think.
What Keyline Safety does
Keyline Safety is a PPE and safety supplier in London, Ontario, serving Canadian workplaces since 1968. For arc flash and electrical work, our range includes:
- Collection: Arc Rated and Flame Resistant Clothing
- Collection: Flame Resistant and Arc Flash Protection
- Product: Atlas Workwear FR/AR Hi Vis Hoodie
- Product: Atlas Workwear FR/AR 4” Coveralls
- Product: Bisley PIP AR/FR Dual-Certified Insulated Parka Jacket (33.3 cal/cm²)
- Product: Atlas Workwear Atlas Thermax FR/AR Knitted Balaclava
- Product: Boss Xtreme AR Rated Goatskin Leather Drivers Glove
- Product: NOVAX Class 0 Rubber Insulating Glove
Check each product page for its stated arc rating before matching it to a task.
Matching arc-rated clothing to your arc flash study? Ask Keyline Safety through our safety assistant chat.
Frequently asked questions
Does CSA Z462 still use arc flash PPE categories?
No. CSA Z462:24 replaced arc flash PPE categories with minimum arc ratings. Former categories 1 to 5 correspond to 4, 8, 25, 40 and 75 cal/cm². NFPA 70E in the U.S. still uses categories, so older labels and documents may show them.
What does cal/cm² mean on arc-rated clothing?
It's the arc rating: the amount of incident energy, in calories per square centimetre, the garment or tested layer system is rated to handle. It must meet or exceed the incident energy or minimum arc rating set for the task.
Can I add the arc ratings of two layers together?
No. The rating of a layered system has to come from testing those layers together. Use the system rating the manufacturer provides, not the sum of the individual labels.
Is FR clothing the same as arc-rated clothing?
No. Arc-rated clothing is flame-resistant, but flame-resistant clothing doesn't necessarily have an arc rating. For arc flash exposure, look for an arc rating in cal/cm² on the label.
Is an arc-rated hoodie enough for arc flash protection?
Only for the body, and only if its arc rating meets the requirement for the task. A hoodie's fabric hood isn't an arc flash hood, so face, head, hand and hearing protection still have to be selected for the same hazard.
Keep reading
- Understanding arc flash: the importance of safety equipment in electrical work
- The importance of lockout/tagout in industrial workplaces
- Cold-weather work in Canada: a PPE and supervisor checklist